The RSP-PV12.5-1000-3P surge arrester from Relpol is a three-pole class I+II protection device designed specifically for DC installations up to 1000 V DC and effective surge protection of DC installations in PV systems. The RSP-PV12.5-1000-3P PV surge arrester is equipped with a visual indication of the protector's technical status (red or green flag) and with an isolated potential-free contact, which allows supervision of the device's failure even from a distance.

 

Technical specifications:

  • Protection type: Type 1 + Type 2 (Class I+II)
  • Number of poles: 3P
  • DC nominal voltage (Un): 1000 V
  • Maximum continuous operating voltage (Uc): 1200 V DC
  • Surge current Iimp (10/350 µs): 12.5 kA
  • Maximum discharge current Iimp (10/350 µs): 80 kA
  • Voltage protection level (Up): ≤ 4.0 kV
  • Connection type: screw terminals
  • Mounting method: on DIN rail 35 mm
  • Operating temperature: from -40°C to +80°C
  • Compliance with standard: PN-EN 61643-31

 

Where to use the RSP-PV12.5-1000-3P?

  • In high-power DC installations
  • In residential and industrial photovoltaic systems
  • In applications requiring a high level of DC surge protection
  • In systems installed in areas with a high risk of lightning strikes

Technical info

Data

Index

2617386

Depth

87

Width mm

54,3

Height mm

88,6

Weight kg

0,581

ETIM class

EC001457

Ip cover

IP20

The RSP-PV12.5-1000-3P surge arrester from Relpol is a three-pole class I+II protection device designed specifically for DC installations up to 1000 V DC and effective surge protection of DC installations in PV systems. The RSP-PV12.5-1000-3P PV surge arrester is equipped with a visual indication of the protector's technical status (red or green flag) and with an isolated potential-free contact, which allows supervision of the device's failure even from a distance.

 

Technical specifications:

  • Protection type: Type 1 + Type 2 (Class I+II)
  • Number of poles: 3P
  • DC nominal voltage (Un): 1000 V
  • Maximum continuous operating voltage (Uc): 1200 V DC
  • Surge current Iimp (10/350 µs): 12.5 kA
  • Maximum discharge current Iimp (10/350 µs): 80 kA
  • Voltage protection level (Up): ≤ 4.0 kV
  • Connection type: screw terminals
  • Mounting method: on DIN rail 35 mm
  • Operating temperature: from -40°C to +80°C
  • Compliance with standard: PN-EN 61643-31

 

Where to use the RSP-PV12.5-1000-3P?

  • In high-power DC installations
  • In residential and industrial photovoltaic systems
  • In applications requiring a high level of DC surge protection
  • In systems installed in areas with a high risk of lightning strikes

Ask for the details of the offer

I consent to the processing of my personal data by Relpol S.A. More information on the processing of personal data in the Privacy Policy*
I have read the Privacy Policy*