Breaking capacity 6 kA • IEC/EN 60898-1 • Mounting on DIN TH35 rail • intended for AC 50/60 Hz circuits with a rated voltage of 230/400 V and a rated current up to 63 A
Breaking capacity 6 kA • IEC/EN 60898-1
• Fork and pin busbar connection (top/bottom)
• Contact position indicator
• Connection capacity 0.5 - 25 mm2
• Mounting on DIN TH35 rail
The RMC6 miniature circuit breaker is intended for AC 50/60 Hz
circuits with a rated voltage of 230/400 V and a rated current up
to 63 A. It provides protection against overload and short circuit
and can also be used for infrequent circuit switching.
The circuit breakers are suitable for industrial and commercial
applications, as well as high-rise and residential buildings and
other applications.
Technical Specification
| Rated current (In) |
1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 A |
| Rated voltage (Ue) |
230/400 V AC |
| Working Frequency |
50/60 Hz |
| Breaking Capacity |
6 kA |
| Poles |
1P, 2P, 3P, 4P |
| Rated insulation voltage (Ui) |
500 V |
| Tripping Curves |
B, C, D |
| Mechanical life |
20 000 switching cycles |