Surge protective devices of the RSP-E12.5-11 series

Technical info

For L–N: impulse current (Iimp) 25 kA (10/350 µs), maximum discharge current (Imax) 100 kA, nominal discharge current 25 kA.

For N–PE: impulse current (Iimp) 50 kA (10/350 µs), maximum discharge current (Imax) 100 kA, nominal discharge current 50 kA.

For single-phase network 1+1, (Uc) 275 V AC.

Protection: MOV varistor for L–N, GDT for N–PE.

The device is equipped with a potential-free contact for remote fault indication.

Width: 36 mm per pole.

• Class I+II / Type 1+2 / B+C surge protective device in accordance with IEC/EN 61643-11.

• Two-pole SPD (1+1 circuit) for use in single-phase installations.

• Plug-in module (18 mm) allowing easy replacement without dismantling the entire device.

• Thermal disconnector ensures fast thermal response and safe disconnection.

• Lightning impulse current up to 12.5 kA (10/350 µs) for L–N, 25 kA (10/350 µs) for N–PE.

• Surge current up to 80 kA (8/20 µs) for L–N, 50 kA (8/20 µs) for N–PE.

• Protection against low voltage conditions.

• High short-circuit current up to 50 kA rms, suitable for use in most AC power supply systems.

• Fault indication due to degradation and optional remote signaling contact.

• Wide operating temperature range: −40°C to +85°C.

• Mounting on 35 mm DIN rail.

Electrical parameters

Maximum continuous operating voltage Uc

L-N / N-PE 275 V AC/ 255VAC

Nominal discharge current (8/20 μs) In

L-N / N-PE 25 kA/25 kA

Maximum discharge current (8/20 μs) Imax

L-N / N-PE 80 kA/ 50 kA

Protection level Up

L-N / N-PE 1,2 kV/ 1,5 kV

Response time

L-N / N-PE ≤ 25 ns / ≤100 ns

Back-up protection

≤ 250 A gL/gG