Surge protective devices of the RSP-E12.5-10

Technical info

Impulse current (Iimp) 25 kA (10/350 µs), maximum discharge current (Imax) 100 kA, nominal discharge current 25 kA.

Single-pole MOV technology with a potential-free contact for remote fault indication in single-phase networks.

Width: 36 mm per pole.

• Class I+II / Type 1+2 surge protective device in accordance with IEC/EN 61643-11.

• Single-pole SPD for multifunctional surge protection.

• Plug-in module (18 mm) allowing easy replacement without dismantling the entire device.

• Thermal disconnector ensures fast thermal response and safe disconnection.

• Lightning impulse current up to 12.5 kA (10/350 µs).

• Surge current up to 80 kA (8/20 µs).

• Protection against low voltage conditions.

• High short-circuit current up to 50 kA rms, suitable for use in most AC power supply systems.

• Fault indication due to degradation and optional remote signaling contact.

• Wide operating temperature range: −40°C to +85°C.

• Mounting on 35 mm DIN rail.

Electrical parameters

Maximum continuous operating voltage Uc

275 V AC

Nominal discharge current (8/20 μs) In

25 kA

Maximum discharge current (8/20 μs) Imax

80 kA

Protection level Up

1,2 kV

Response time 

≤ 25 ns

Back-up protection

≤ 250 A gL/gG

 