Contacts: 1CO, 1NO; rated load AC1 (1NO) 30 A /240 V AC; for PCB; DC coils of up to 110 V DC, High load 30 A
| Contact data |
||
| Number and type of contacts |
1 CO, 1 NO |
|
| Rated / max. switching voltage |
AC: 240 V / 300 V ; DC: 110 V / 110 V |
|
| Rated load (capacity) |
AC1 - 1 NO: 30 A / 240 V AC; DC1- 1 NO: 30 A / 14 V DC |
|
| Coil data |
||
| Rated voltage |
DC: 5, 12, 24, 48, 110 V |
|
| Rated power consumption |
DC: 0,9 W |
|
| General data |
||
| Electrical life resistive |
AC1: 105 1 NO: 30 A, 240 V AC |
|
| Mechanical life (cycles) |
107 |
|
| Ambient temperature operating |
-55...+100 oC |
|