1,2,3,4 -pole lightning and surge arresters limp = 12,5 kA/ pole. Max. continuous operating voltage 275 V AC, Max. discharge current 60 kA
• for protecting low voltage equipment against lightning and surge damages
• for installation in conformity with the lightning protection zones concept at LPZ 0-1
• designed according to IEC 61643-11:2011
Max. continuous operating voltage Uc |
275 V AC |
Nom. discharge current (8/20 μs) In |
30 kA |
Max. discharge current (8/20 μs) Imax |
60 kA |
Impulse discharge current (10/350 μs) Iimp |
12,5 kA |
Voltage protection level Up |
≤ 2 kV |
Response time ta |
≤ 100 ms |
TOV withstand (5 s) Ut |
355 V |
Index |
Product |
Number of poles |
2617119 |
RSP-T1T2-AC 12.5/1P |
1 pole |
2617120 |
RSP-T1T2-AC 12.5/2P |
2 poles |
2617121 |
RSP-T1T2-AC 12.5/3P |
3 poles |
2617122 |
RSP-T1T2-AC 12.5/4P |
4 poles |
2617123 |
RSP-T1T2-AC 12.5/1P +NPE |
2 poles (1+NPE) |
2617124 |
RSP-T1T2-AC 12.5/3+NPE |
4 poles (3+NPE) |