Overvoltage arrester RSP-4L-.. NEW

Technical info

 

RSP-4L-5

RSP-4L-12

RSP-4L-24

RSP-4L-48

Rated operating voltage Un

5  V DC

12 V DC

24 V DC

48 V DC

Maximum continuous operating voltage Uc

6 V DC 

4,2 V AC

15 V DC

10,6 V AC

33 V DC

23,3 V AC

54 V DC

38 V AC

Rated load current at 25 °C IL

0,5 A

D1 current impulse (10/350 μs, per line) Iimp

0,5 kA

   

Ambient temperature (operating) Ta

-40... +80 oC

Mounting

 

Cover protection category

IP20

Dimensions (L x W x H)

95 x 7 x 98 mm

Weight

68 g