Function ER

ER - ON delay and OFF delay with control contact S. Independent settings of T1 and T2 intervals.

The input of the time relay is supplied with voltage U continuously. Closing of the control contact S starts the interval T1, and after it has lapsed, the output relay R switches on. Opening of the control contact S starts the interval T2, and after it has lapsed, the output relay R switches off. In case the control contact S is closed in the course of the interval T2, the measured time is reset and the output relay R remains switched on. In case the control contact S is closed for time shorter than T1, the unit will not switch the output relay R on.

 

Relays performing the function "ER": MT-W...RPC-1ER-...