Max. discharge current: 50 kA. Category IEC / EN / VDE: class I+II, II / type 1+2, 2 / B+C, C. Protection methods: (+)-PE, (-)-PE, (+)-(-). Protective elements: MOV. Enclosure: modular.
• For the protection of low-voltage devices against lightning strikes and surges,
• For installation according to the lightning protection zone (LPZ) concept in LPZ 0-1,
• Designed in accordance with the IEC 61643-31:2018 standard.
• Surge protection devices protect against lightning-induced surges in solar systems (photovoltaic power systems),
• These units must be installed in parallel in DC networks that need to be protected and provide both common and differential protection modes,
• Their location is recommended at both ends of the DC power line (on the solar panel side and the inverter/transformer side), especially if the line is external and long.
• RSP-T...-DC.../... is an SPD of class I+II, II for low-voltage power systems,
• Primarily installed in the main distribution cabinet,
• The surge protectors are equipped with high-energy MOV (metal oxide varistors) with special thermal disconnectors and associated fault indicators.
RSP-T1T2 -DC 9/3P |
RSP-T1T2 -DC 6.25/3P |
|
Maximum continuous operating voltage Uc |
1000 V DC |
|
Nominal discharge current (8/20 μs) In |
20 kA |
|
Maximum discharge current (8/20 μs) Imax |
50 kA |
|
Peak current (10/350 μs) Iimp |
9 kA |
6,25 kA |
Protection level Up |
4,5 kV |
|
Response time |
≤ 100 ns |
|
Ambient temperature (operation) |
-40...+80 °C (parallel connection) / -40...+60 °C (through connection) |
|
Cross-sectional area of wires connected to terminals |
35 mm² (solid) / 50 mm² (stranded) |
Index |
Commercial code |
Number of poles |
2617144 |
RSP-T1T2 -DC 9/3P |
3-pole |
2617145 |
RSP-T1T2 -DC 6.25/3P |
3-pole |