Time relays MT-TIP-...

Technical info

Contact data 

Number and type of contacts

1 C/O

Contact material

AgSnO2

Max. switching voltage 

AC

400 V

DC

300 V

Rated load

AC1

10 A / 250 V AC

Max. breaking capacity

AC1

16 A / 250 V AC

Input control circuit 

Rated voltage

AC: 50/60 Hz AC/DC 

12…240 V

Insulation 

Insulation rated voltage

 

250 V AC

Rated surge voltage

 

2 500 V 1,2 / 50 µs 

Dielectric strength: 

- input - output

2 500 V AC

- contact clearance

1 000 V AC

General data 

Ambient temperature operating 

-20...+45 oC

Time module data 

Functions: li + lp (Cyclical operation in two independent intervals T1 and T2)

Time ranges

 0,1s ...100 h

Min. time of pulse duration

 AC ≥ 50 ms, DC ≥ 20 ms