Monitoring relay MR-EU1W1P

Technical info

Meassuring circuit data

Functions

UNDER, WIN

minimum value supervision with the histeresis mode

LED indicator

green LED, yellow LED, red LED

Meassuring circuit 

• measuring variable

DC or AC sinus, 48…63 Hz

• terminals, measuring input 

230 V AC; terminals E-F3

24V AC; terminals E-F2

24V DC; terminals E-F1

• overload capacity

≥ 1,2 Un

• swiching threshold Us

max: 0,8< In < 1,2  min: 0,75 < In < 1,15

Input circuit 

Supply voltage U 

230 V AC; terminals E-F3

24V AC; terminals E-F2

24V DC; terminals E-F1

Rated power consumption

230 V AC: 10,0 VA / 0,6 W 24 V AC: 1,3 VA / 0,8 W 24 V DC: 0,6 W 

Rated frequency

AC: 48...63 Hz

Output circuit 

Number and type of contacts

1 C/O - changeover

Rated load AC1

5 A / 250 V AC

Max. breaking capacity AC1

1 250 VA

Insulation 

Rated surge voltage

4 000 V AC

Overvoltage category

III PN-EN 60664-1

Insulation pollution degree 

2, if built-in 3 PN-EN 60664-1