Monitoring relay MR-GI3M2P-TR2

Technical info

Meassuring circuit data 

Functions

OVER, OVER+LATCH, UNDER, UNDER+LATCH, WIN, WIN+LATCH 

timing adjustment for start-up suppression time and tripping delay

Time intervals (timing adjustment) 

start-up suppression time (0...10 s) tripping delay (0,1...10 s)

LED indicator

yellow LED, green LED, red LED

Meassuring circuit 

• measuring variable

AC sinus, 48...63 Hz

• measuring input

5AAC  zaciski: K-I1, K-I2, K-I3

• overload capacity

6AAC

• input resistance

10 mΩ

• swiching threshold Us

max: 0,1< In < 1,0  min: 0,05 < In < 0,95

Input circuit 

Supply voltage U

12 … 400 V AC; terminals A1-A2

Rated power consumption

2,0 VA / 1,5 W

Rated frequency

as per the specification of TR2 supply transformer

Output circuit 

Number and type of contacts

2 C/O - changeover

Rated load AC1

5 A / 250 V AC

Max. breaking capacity AC1

1 250 VA

Insulation 

Rated surge voltage

4 000 V AC

Overvoltage category

III wg PN-EN 60664-0

Insulation pollution degree

3 wg PN-EN 60664-1