Relay R40N

Technical info

Contact data

Number and type of contacts

1 CO, 1 NO

Rated switching voltage

AC:  240 V;  DC: 110 V

Rated load (capacity)

AC1: 1 NO: 40 A / 240 V AC;  DC1: 1 NO: 40 A / 30 V DC  

Coil data

Rated voltage

AC: 12 ... 220 V:  DC: 5 ... 110 V

Rated power consumption

AC: 2,0 VA;  DC: 0,9 W

General data

Electrical life resistive

AC1: 105  1 NO: 40 A, 240 V AC

Mechanical life (cycles)

107

Ambient temperature operating  

-55...+100 oC